CODESYS Safety for EtherCAT Safety Module SL

CODESYS extension for EtherCAT-based safety solutions with TwinSAFE logic modules EL6900, EL6910 and EK1960 from Beckhoff under a CODESYS controller with CODESYS EtherCAT Master Stack.

Current version : 4.3.2.0
Article number  : 2306000000
Categories: ,

Description

The TÜV-certified product allows any CODESYS project to be expanded with an EtherCAT controller with CODESYS EtherCAT Master Stack for the development of safety functions with TÜV-certified safety logic modules from Beckhoff and digital FSoE I/O modules and analog TSC input modules in the EtherCAT network. The expansion with safety-specific editors and configurators is seamlessly integrated into the CODESYS development system and the CODESYS EtherCAT configurator. It enables the cost-effective and scalable implementation of simple safety applications with zero system integration or adaptation effort and low acceptance effort. The product is aimed at users and device manufacturers who do not plan to develop their own safety controller and only require limited safety functionality.

  • Safety level up to PL-e according to DIN EN ISO 13849 and up to SIL3 according to IEC 62061/61508, depending on input and output devices and programmed logic.
  • Simplified acceptance through Limited Variability Programming (LVL) according to ISO 13849 and IEC 62061.
  • Logic modules : EL6900 or EL6910 as EtherCAT terminal (TwinSAFE-Logic), or EK1960 as EtherCAT coupler (TwinSAFE-Compact Controller) from Beckhoff, or EL1918, EL2912, EL2911
  • Digital SIL3 I/O modules : FSoE modules (Failsafe over EtherCAT) from any manufacturer installed from EtherCAT description files.
  • Analog SIL2 input modules : 10 TSC modules (TwinSAFE SingleChannel) from Beckhoff: EL3124-0090, EL3174-0090 (differential), EL3214-0090 (for resistance sensors), EL3314-0090 (for thermocouple), EL3356-0090 (for load cell/resistance bridge); and encoders EL5001-0090 (SSI), EL5021-0090 (Sin/Cos), EL5032-0090 (EnDat2.2), EL5101-0090 (incremental differential RS422), EL5151-0090 (incremental).

Operating functions and fieldbus configuration on the EtherCAT controller can be changed without affecting the safety functions of the safety logic module.

  • Standard signals can be exchanged with the EtherCAT controller: standard input signals for comparison with TSC signals, signals from/to the standard application.
  • Multiple safety logic modules possible within an EtherCAT network.
  • Groups : Monitoring of several safety areas by a safety logic module supported by structuring the safety application into “groups” of I/O modules and associated logic in an IEC 61131-3 POU in FUP. Each group is started, stopped, diagnosed and error acknowledged individually by the standard application.
  • Optional devices : If a safety area is not present in the machine, EL6910 and EK1960 allow the corresponding group to be deactivated via online command without changing the application (permanent, temporary, passivated).

Requirements

Programming system CODESYS V3.5 SP15 Patch 4 (64 bit, 32 bit),

or a version from the “Compatibility” column under “All Versions”

Not to be used with GIT or SVN extension.

Programming platform Windows 10 (64-bit)

The versions maintained by Microsoft are supported.

Runtime system CODESYS Control V3.5 SP4 (or higher)
Additional requirements License for CODESYS EtherCAT Master on controller
Supported devices
  • 3 logic modules: EL6900, EL6910, EK1960 (Beckhoff TwinSAFE-Logic, TwinSAFE-Compact Controller)
  • Logic modules as FSoE I/O modules: EK1960, EL1918, EL2912, EL2911
  • installed FSoE I/O modules (without/preconfigured SRA parameters)
  • 10 analog TSC input modules: EL3124-0090, EL3174-0090, EL3214-0090, EL3314-0090, EL3356-0090, EL5001-0090, EL5021-0090, EL5032-0090, EL5101-0090, EL5151-0090 (B eckhoff TwinSAFE SingleChannel)

Note: Use the Device Reader project to determine the functions supported by the controller. Device Reader is available free of charge from the CODESYS Store.

restrictions No configuration of SRA parameters; no installation of additional TSC modules from description files; no PROFIsafe support.
Licensing Single device license: The license can be used on the controller on which the CODESYS runtime system is installed.

The license is activated on a software-based license container (soft container) that is permanently linked to the controller. Alternatively, the license can be stored on a CODESYS key (USB dongle). The license can be used on another controller by replugging the CODESYS key.

Note: Without a license, the software runs in demo mode for two hours. SAFE STATE WILL BE REACHED AFTER TWO HOURS!

Required accessories Optional: CODESYS Key

Additional information

Article no :

2306000000