CODESYS Control for PFC200 SL

The product enables the end user to program various models of a WAGO PFC200 controller with the free development environment CODESYS Development System (V3).

Current version : 4.11.0.0
Item number : 2302000010-SW

Category:

Description

CODESYS Control for PFC200 SL is a CODESYS V3-based SoftPLC for the WAGO PFC200 industrial control system. The control can be configured with the CODESYS Development System (V3) after installing the runtime environment.

  • Download the product “CODESYS Control for PFC200 SL” from the CODESYS Store (http://store.codesys.com)
  • Installation of the CODESYS SoftPLC on a WAGO PFC200 device (http://www.wago.com)
  • Replacement of the WAGO PLC runtime environment, as included in WAGO’s scope of delivery, with a standard CODESYS V3 compatible SoftPLC
  • Configuration of the control using the WAGO software tools

To use

  • Suitable for controls in the factory automation and process automation sectors, with a newly defined range of functions for the control
  • Comprehensive engineering solution with the free CODESYS Development System (V3), expandable with add-ons from the CODESYS Store
  • Efficient engineering with the products of the CODESYS Professional Developer Edition (code management via Apache Subversion connection, static code analysis, runtime measurement on the controller, CODESYS Test Manager for test automation, methodical application development with UML diagrams)
  • Same performance and cycle times of the fieldbus tasks as the OEM product, e.g. B. when using local I/O modules

Detailed information can be found in the CODESYS online help.

Interfaces

  • CODESYS OPC UA Server, as a full version for data exchange.
  • Support for all common digital and analog input and output modules from WAGO (list available for download in the CODESYS Store)

Visualization

  • CODESYS WebVisu is included as a full version in the delivery of the runtime package.

SL Extension

The SL Extension Package is included in the runtime package and offers additional functions:

  • Connection of existing C code
  • Implementation of external functions
  • Support start/stop switch
  • Connection of local I/Os
  • Use of external event tasks
  • Connection of persistent storage (retains)

Range of functions

The following fieldbuses are supported when the runtime package is delivered:

  • CODESYS CANopen Manager / Device (except 750-8202 / -8212)
  • CODESYS EtherCAT Master
  • CODESYS EtherNet/IP scanner/adapter
  • CODESYS J1939
  • CODESYS Modbus TCP master/slave
  • CODESYS Modbus Serial Master / Slave (750-8202 / -8212 only)
  • CODESYS PROFINET Controller / Device

Product options

Additional products can be re-licensed for a fee:

  • CODESYS KNX SL
  • CODESYS Redundancy SL

Requirements

Programming system

CODESYS Development System V3.5.19.10 or higher

Supported platforms/devices

  • 750-8202 / -8212 (PFC200 CS 2ETH RS)

  • 750-8203 / -8213 (PFC200 CS 2ETH CAN

  • 750-8204 / -8114 (PFC200 CS 2ETH RS CAN)

  • 750-8206 / -8216 (PFC200 CS 2ETH RS CAN DPS)

  • 750-8207 (PFC200 CS 2ETH RS Mobilfunk)

  • 750-8215 (PFC200 G2 4ETH CAN USB)

Note: Use the “Device Reader” tool to determine the functions supported by the controller (free part of the CODESYS Development System).

Additional requirements

See License Agreement. After installation, the user is responsible for ensuring that the combination of software package and hardware is used and functions according to his device specifications.

  • Minimale WAGO Firmware Version 17

  • Dynamic libraries required by the CODESYS Control Runtime Binary:

restrictions

  • The telecontrol technology protocols are not supported.

  • Not suitable for use in containers or virtual machines (VMs)!

Licensing

Single device license: The license can be used on the controller on which the CODESYS runtime system is installed.


The license activation takes place on a software-based license container (soft container) that is firmly tied to the controller. Alternatively, the license can be stored on a CODESYS key (USB dongle). By changing the CODESYS key, the license can be used on another controller.

Note: Without a license, the software runs in demo mode for two hours. A manual restart is then required.

Required accessories

-

Additional information

Article no :

2302000010-SW